The Flowline US03-0011-00 is a Reflective Ultrasonic Multi-Function Liquid Level Transmitter designed for industrial liquid-level measurement, monitoring or control applications. Use the exact model number when comparing replacement or new-installation requirements, because connection, output, range and enclosure options can vary across Flowline configurations.
Performance and Construction Highlights
- Offered in 1.5m (4.9’) and 3m (9.8’) measurement ranges
- Reflective Technology™ measures reliably with condensation
- Narrow 2” (5cm) beam width for applications with limited space
- Configuration is easy with WebCal software and USB adapter
- Short 1.5” (3.8cm) dead band maximizes tank filling capacity
- PVDF transducer and PP enclosure for corrosive environments
System Integration
Match the model to the controller, PLC, relay, display or other receiving equipment used in the system. Confirm signal type and power requirements from the product documentation before wiring. Mechanical fit and process compatibility should also be verified before installation.
Before purchase, compare the complete model code with the application requirements. Check tank dimensions, process connection, wetted materials, power or signal needs, measurement range and environmental conditions where those values apply. This helps prevent selecting a similar-looking Flowline model with a different configuration.
Service-Friendly Ordering
For maintenance teams, integrators and OEM users searching for Flowline US03-0011-00, the model-specific identification makes it easier to match the product to a documented Flowline level-control system without relying on appearance alone.
For replacement work, record the existing model number and wiring or mounting arrangement before removal. For new projects, review the documented installation guidance and leave adequate clearance around the sensing area. Commission the device using the applicable Flowline instructions and verify the output or switching behavior before returning the process to normal operation.
| Part No | US03-0011-00 |
|---|---|
| Brand | Flowline |
| Product Type | Level Transmitter |
| Product Family | EchoPod |
| Type | Level Transmitter |
| Range | 4” to 9.8’ (10.1cm to 3m) |
| Accuracy | ± 0.2% of range |
| Resolution | 0.039” (1mm) |
| Dead Band | 4in (10.1cm) |
| Beam Width | 2in (5cm) |
| Configuration | WebCal® PC Windows® USB® 2.0 |
| Memory | Non-volatile |
| Supply Voltage | 14-28 VDC |
| Consumption | - |
| Loop Resistance | 500 ohms @ 24 VDC |
| Signal Output | 4-20mA, two-wire |
| Signal Invert | 4-20mA or 20-4mA |
| Signal Fail-safe | 4mA, 20mA, 21mA, 22mA, Hold last |
| Contact Type | - |
| Contact rating | - |
| Contact fail-safe | - |
| Hysteresis | - |
| Process Temperature (F) | -40° to 176° |
| Process Temperature (C) | -40° to 80° |
| Ambient Temperature (F) | -31° to 140° |
| Ambient Temperature (C) | -35° to 60° |
| Pressure | 30 psi (2 bar) |
| Enclosure Rating | Type 6P (IP68) |
| Enclosure Material | Polypropylene |
| Transducer Type | Reflective |
| Transducer Material | Polyvinylidene Fluoride |
| Cable Jacket Material | Polyurethane |
| Cable Type | 4-conductor, Shielded |
| Cable Length | 48in (1.2m) |
| Process Mount | 2in G |
| Mount Gasket | Viton® |
| Classification | Intrinsically Safe |
| Compliance | Automatic |
| Temp. comp | CE, RoHS |
| Approvals | CSA for Canada: Class I, Division 1, Groups A, B, C and D T4; Class II, Division 1, Groups E, F and G T4; Class III, T135C; Ex ia IIC T4 Ga; Ex ia IIIC, T135C Da; CSA for U.S.: Class I, Division 1, Groups A, B, C and D T4; Class II, Division 1, Groups E, F and G T4; Class III, T135C; Class I, Zone 0, IIC AEx ia T4 Ga; Class II, Zone 20, IIIC AEx ia, T135C Da |
| Entity parameters | Install per control drawing #610126 |
| USB Adapter | w/o Fob |
| Series | US01-03 |