Flowline UG01-0001-41 Liquid Level Sensor | Liquid Level Control
Flowline UG01-0001-41 Liquid Level Sensor for Industrial Liquid Level Monitoring, Tank Automation and Process Control
Use Flowline UG01-0001-41 Liquid Level Sensor for industrial level applications. Confirm range, mounting, output and process compatibility before
Industrial Level Control with Flowline UG01-0001-41
The Flowline UG01-0001-41 is a Reflective Ultrasonic Multi-Function Liquid Level Sensor Transmitter Reflective Ultrasonic Multi-Function Liquid Level Sensor Transmitter,4mA, 20mA, 21mA, 22mA, hold last, WebCal PC Windows USB 2.0 designed for industrial liquid-level measurement, monitoring or control applications. Use the exact model number when comparing replacement or new-installation requirements, because connection, output, range and enclosure options can vary across Flowline configurations.
Where This Model Fits
This Flowline configuration is intended for level-related process applications where reliable model matching and documented installation parameters are important. It may be used as part of monitoring, alarm, pump-control or measurement systems depending on the model configuration.
Documented Features
- Offered in 1.5m (4.9') and 3m (9.8') measurement ranges
- Fail-safe diagnostics with selectable relay and signal outputs
- Narrow 2" (5cm) beam width for applications with limited space
- Corrosion resistant PVDF transducer and compact PP enclosure
- Short 1.5" (3.8cm) dead band maximizes tank filling capacity
- Automatic temperature compensation from -40° to 80° C.
Before purchase, compare the complete model code with the application requirements. Check tank dimensions, process connection, wetted materials, power or signal needs, measurement range and environmental conditions where those values apply. This helps prevent selecting a similar-looking Flowline model with a different configuration.
Ordering Checklist
- Confirm part number UG01-0001-41
- Compare range and connection requirements
- Verify electrical/output requirements when applicable
- Check wetted-material compatibility with the process
For maintenance teams, integrators and OEM users searching for Flowline UG01-0001-41, the model-specific identification makes it easier to match the product to a documented Flowline level-control system without relying on appearance alone.
| Part No | UG01-0001-41 |
|---|---|
| Brand | Flowline |
| Product Type | Liquid Level Sensor |
| Series | UG01 |
| Range | 1.5" to 4.9' (3.8cm to 1.5m) |
| Accuracy | 0.125" (3mm) |
| Resolution | 0.019" (0.5mm) |
| Dead band | 1.5" (3.8cm) |
| Beam width | 2" (5cm) |
| Configuration | WebCal® PC Windows® USB® 2.0 |
| Memory | Non-volatile |
| Supply voltage | 14-28 VDC |
| Max. consumption | 0.5W |
| Loop resistance | 500 ohms @ 24 VDC |
| Signal output | 4-20mA, two-wire |
| Signal invert | 4-20mA or 20-4mA |
| Signal fail-safe | 4mA, 20mA, 21mA, 22mA, hold last |
| Contact type | (4) SPST relays |
| Contact rating | 60 VA, 1A maximum |
| Contact fail-safe | Open, closed, hold last |
| Contact hysteresis | Selectable |
| Process temp. | F: -40° to 176°, C: -40º to 80° |
| Temp. comp. | Automatic |
| Ambient temp. | F: -31° to 140°, C: -35° to 60° |
| Pressure | 30 psi (2 bar) |
| Enclosure rating | Type 6P (IP68) |
| Encl. material | Polypropylene |
| Transducer type | Reflective |
| Transducer mat. | Polyvinylidene fluoride |
| Cable jacket mat | Polyurethane |
| Cable type | 9-conductor, shielded |
| Cable length | 48" (1.2m) |
| Process mount | -0001: 2" NPT, -0011: 2" G |
| Mount gasket | -0001: N/a, -0011: Viton |
| Classification | General purpose |
| Approval | UL 61010-1 |
| Compliance | CE, RoHS |