Flowline LU28-01 EchoSonic Ultrasonic Level Transmitter | Liquid
Flowline LU28-01 EchoSonic Ultrasonic Level Transmitter for Industrial Liquid Level Monitoring, Tank Automation and
Use Flowline LU28-01 EchoSonic Ultrasonic Level Transmitter for industrial level applications. Confirm range, mounting, output and process
Flowline LU28-01 for Liquid Level Systems
The Flowline LU28-01 is a Ultrasonic Level Transmitter EchoSonic Ultrasonic Level Transmitter, Sensor range , Process mount NPT (US), Mount gasket Viton designed for industrial liquid-level measurement, monitoring or control applications. Use the exact model number when comparing replacement or new-installation requirements, because connection, output, range and enclosure options can vary across Flowline configurations.
Performance and Construction Highlights
- Offered in 4 measurement ranges from 9.8 Inch (3m) to 32.8 Inch (10m)
- DSP auto adaptive filters enable plug and play operation optimizing signal output filtering and obstacle recognition
- Submersible type 6P enclosure is ideal for sump and below grade installations
- Configuration is fast and easy via WebCal software and USB adapter
- Narrow 2 Inch or 3 Inch beam width for applications with limited measurement space
- Short 4 Inch or 8 Inch dead band maximizes the measurable filling capacity of the tank
System Integration
Match the model to the controller, PLC, relay, display or other receiving equipment used in the system. Confirm signal type and power requirements from the product documentation before wiring. Mechanical fit and process compatibility should also be verified before installation.
Before purchase, compare the complete model code with the application requirements. Check tank dimensions, process connection, wetted materials, power or signal needs, measurement range and environmental conditions where those values apply. This helps prevent selecting a similar-looking Flowline model with a different configuration.
Service-Friendly Ordering
For maintenance teams, integrators and OEM users searching for Flowline LU28-01, the model-specific identification makes it easier to match the product to a documented Flowline level-control system without relying on appearance alone.
For replacement work, record the existing model number and wiring or mounting arrangement before removal. For new projects, review the documented installation guidance and leave adequate clearance around the sensing area. Commission the device using the applicable Flowline instructions and verify the output or switching behavior before returning the process to normal operation.
| Part No | LU28-01 |
|---|---|
| Brand | Flowline |
| Product Type | Ultrasonic Level Transmitter |
| Product Family | EchoSonic |
| Type | Level Transmitter |
| Accuracy | ±0.2% of range |
| Configuration | WebCal PC Windows USB 2.0 |
| Memory | Non-volatile |
| Supply Voltage | 24 VDC (loop) |
| Consumption | 0.5W |
| Loop Resistance | 500 ohms @ 24 VDC |
| Signal Output | 4-20 mA, two-wire |
| Signal Invert | 4-20 mA or 20-4 mA |
| Signal Fail-safe | 4 mA, 20 mA, 21 mA, 22 mA or hold last |
| Process Temperature | F: -4° to 140° C: -20° to 60° |
| Temperature Comp | Automatic |
| Ambient Temperature | F: -31° to 140°, C: -35° to 60° |
| Pressure | MWP = 30 PSI (2 bar) |
| Enclosure Rating | Type 6P, encapsulated, corrosion resistant & submersible |
| Enclosure Material | Polycarbonate |
| Trans Material | PVDF |
| Cable Jacket Material | Polyurethane |
| Cable Type | 4-conductor, shielded |
| Cable Length | 10ft (3m) |
| Mount gasket | Viton |
| Classification | General purpose |
| Compliance | CE, RoHS |
| Approvals | cFMus |