Flowline LO10-1405 for Liquid Level Systems

The Flowline LO10-1405 is a Switch-Tek Optic Leak Detection Switch designed for industrial liquid-level measurement, monitoring or control applications. Use the exact model number when comparing replacement or new-installation requirements, because connection, output, range and enclosure options can vary across Flowline configurations.

Performance and Construction Highlights

  • Fail-safe leak sensor inverts wet to alert user for maintenance
  • Rugged PP or PFA Teflon probe and cable
  • 1A relay selectable NO or NC via power supply wiring polarity
  • Compatible with MicroPoint multi-channel indicator

System Integration

Match the model to the controller, PLC, relay, display or other receiving equipment used in the system. Confirm signal type and power requirements from the product documentation before wiring. Mechanical fit and process compatibility should also be verified before installation.

Before purchase, compare the complete model code with the application requirements. Check tank dimensions, process connection, wetted materials, power or signal needs, measurement range and environmental conditions where those values apply. This helps prevent selecting a similar-looking Flowline model with a different configuration.

Service-Friendly Ordering

For maintenance teams, integrators and OEM users searching for Flowline LO10-1405, the model-specific identification makes it easier to match the product to a documented Flowline level-control system without relying on appearance alone.

For replacement work, record the existing model number and wiring or mounting arrangement before removal. For new projects, review the documented installation guidance and leave adequate clearance around the sensing area. Commission the device using the applicable Flowline instructions and verify the output or switching behavior before returning the process to normal operation.

Specification
Part NoLO10-1405
BrandFlowline
Product TypeLevel Switch
OrientationUniversal
Accuracy+/- 1 mm in water
Repeatability+/- 0.5 mm in water
Supply voltage12-36 VDC
Consumption25 mA maximum
Contact typeSPST relay
Contact rating60 VA
Contact outputSelectable NO/NC
Process temperatureF: -40° to 176°, C: -40° to 80°
Pressure150 psi (10 bar) @ 25°, derated @ 1.667 psi (.113 bar) per°. above 25°.
Sensor ratingNEMA 6 (IP68): PP NEMA 4X (IP65): PFA
Sensor material1XX5: PP, 2XX5: PFA
Cable jacket material1XX5: PP, 2XX5: PFA
Cable type4-conductor, #22 AWG (shielded)
Cable lengthStandard: 10ft (3m) Special order: 25ft (7.6m) or 50ft (15.2m)
Process mount3/4
Mount. gasketViton (G version only)
ClassificationGeneral purpose
CE complianceEN 61326 EMC EN 61010-1 safety
Documents