Flowline LC10-1051 Level Controller | Liquid Level Control System
Flowline LC10-1051 Level Controller for Industrial Liquid Level Monitoring, Tank Automation and Process Control
Use Flowline LC10-1051 Level Controller for industrial level applications. Confirm range, mounting, output and process compatibility before purchase.
Industrial Level Control with Flowline LC10-1051
The Flowline LC10-1051 is a Switch-Pro Compact Level Controller designed for industrial liquid-level measurement, monitoring or control applications. Use the exact model number when comparing replacement or new-installation requirements, because connection, output, range and enclosure options can vary across Flowline configurations.
Where This Model Fits
This Flowline configuration is intended for level-related process applications where reliable model matching and documented installation parameters are important. It may be used as part of monitoring, alarm, pump-control or measurement systems depending on the model configuration.
Documented Features
- Fail-safe relay control of pumps or valves with 0-60 second delay
- Optional strobe brings immediate attention to level alarm conditions
- Polypropylene enclosure rated NEMA 4X with swivel base for conduit alignment
- Easy setup with LED indicators for sensor, power and relay status
- Invert switch changes relay state from NO to NC without rewiring
- Connects to any Flowline level switch
Before purchase, compare the complete model code with the application requirements. Check tank dimensions, process connection, wetted materials, power or signal needs, measurement range and environmental conditions where those values apply. This helps prevent selecting a similar-looking Flowline model with a different configuration.
Ordering Checklist
- Confirm part number LC10-1051
- Compare range and connection requirements
- Verify electrical/output requirements when applicable
- Check wetted-material compatibility with the process
For maintenance teams, integrators and OEM users searching for Flowline LC10-1051, the model-specific identification makes it easier to match the product to a documented Flowline level-control system without relying on appearance alone.
| Part No | LC10-1051 |
|---|---|
| Brand | Flowline |
| Product Type | Level Controller |
| Supply voltage | 120 / 240 VAC, 50-60 Hz |
| Consumption | 0.25A maximum |
| Sensor inputs | LC10: two-wire level switch / LC11: two-wire level switches |
| Sensor supply | 13.5 VDC @ 27 mA |
| LED indication | Sensor, power & relay |
| Strobe type | -10X1: N/A -10X2: Xenon tube |
| Strobe flash | -10X1: N/A -10X2: (1) per second |
| Contact type | LC10: (1) SPDT relay LC11: (1) SPDT relay, latching |
| Contact rating | 250 VAC @ 16A |
| Contact output | Selectable NO / NC |
| Contact delay | 0-60 seconds |
| Contact latch | LC10: N/A LC11: Selectable ON / OFF |
| Ambient temperature | F: -40° to 140°, C: -40° to 60° |
| Enclosure rating | NEMA 4X (IP65) |
| Enclosure material | -10X1: PP, UL94VO -10X2: PP, UL94VO & PC |
| Conduit entrance | 1/2in NPT |
| Enclosure mount | 3/4in NPT (3/4in Rp) |
| Classification | General purpose |
| Compliance | CE |
| Approvals | CSA, LR 79326 |