Flowline LC52-1001 Level Display & Controllers LC52-1001
LC52 Series Level Display & Controllers of Flowline
SKU:LC52-1001
Model Number: LC52-1001
$545.000
Flowline DataPoint LC52-1001 Level Controller. Supply voltage Selectable 120 / 240 VAC 50-60 Hz
Application
The general purpose controller provides single tank level indication with 2 relays, 1-3 set points and an isolated analog repeater. Relay 1 is configurable on a single set point. Relay 2 can be configured on a single set point or latched on two set points for automatic fill or empty control. Package the controller with any of our level transmitters. The NEMA 4X polycarbonate enclosure is a great choice for field mount installations and comes complete with a DIN rail mounting kit.
Features:
- 3.5 digit LED display indicates level in custom engineering units
- Fail-safe relay control of pumps or valves with 0-60 second delay
- Easy set up with push button calibration for span, display and relay set points
- 35 mm DIN rail mount polypropylene enclosure with removable terminal strips
- Invert switch changes relay state from NO to NC without rewiring
Key Benefits:
- Simple controller for operating 2 alarms or 1 auto fill/empty with alarmy
- Bar graph provides instant confirmation of transmitter's operational performance
- Lock-out feature prevents inadvertent button pushing from changing settings
| Display type | LED, 3.5 digit |
|---|---|
| Display units | Engineering |
| Display output | 0 to 999 |
| LED indication | Power & relay |
| LED bar graph | Span and set points |
| Memory | Non-volatile |
| Security | Set point lock out |
| Configuration | Push button |
| Alarm indication | Amber: < 4mA Red: > 20 mA |
| Sensor input | 4-20 mA |
| Supply voltage | Selectable 120 / 240 VAC 50-60 Hz |
| Sensor supply | 24 VDC @ 1.5 watts |
| Loop power | 4-20 mA, 18 VDC |
| Consumption | 5 watts maximum |
| Contact type | SPDT relays (one latching) |
| Contact rating | 250 VAC @ 10A |
| Contact output | Selectable NO / NC |
| Contact latch | Selectable ON / OFF |
| Contact delay | 0-60 seconds |
| Repeater output | 4-20 mA, 12-36 VDC |
| Ambient temperature | F: -40° to 158°, C: -40° to 70° |
| Enclosure type | 35mm DIN rail (EN 50 022) |
| Enclosure material | PP, UL94VO |
| Classification | General purpose |
| Compliance | CE |